VRE - Mechanisms
BEN - Remotely controlled servomotor
The BEN servomotor is specifically designed for remote control of smoke control dampers.
- Access for manual operation
- Plug (ST)
Variants
-
BEN24
Servomotor BEN 24V -
BEN230
Servomotor BEN 230V
Unlocking
-
manual unlocking
turn the enclosed handle anticlockwise (VRE; VU120) or clockwise (MARKAGE MB; VUW120). -
remote unlocking
power cables 1 and 2.
Resetting
-
manual resetting
turn the enclosed handle clockwise (VRE; VU120) or anticlockwise (MARKAGE MB; VUW120). -
motorised resetting
power cables 1 and 3.
BEE - Remotely controlled servomotor
The BEE servomotor is specifically designed for remote control of smoke control dampers.
- Access for manual operation
- Plug (ST)
Variants
-
BEE24
Servomotor BEE 24V -
BEE230
Servomotor BEE 230V
Unlocking
-
manual unlocking
turn the enclosed handle anticlockwise (VRE) or clockwise (MARKAGE MB). -
remote unlocking
power cables 1 and 2.
Resetting
-
manual resetting
turn the enclosed handle clockwise (VRE) or anticlockwise (MARKAGE MB). -
motorised resetting
power cables 1 and 3.
BEE-SR-10V - Remotely controlled modulating actuator
The BEE-SR-10V modulating actuator is specifically designed for remote control of smoke control dampers. The position of the damper blade is adjustable by means of a 0 to 10 V connection.
- Access for manual operation
Variants
-
BEE24-SR-10V
Modulating actuator BEE24-SR-10V for the control of the airflow
Unlocking
-
manual unlocking
turn the enclosed handle anti-clockwise. -
remote unlocking
apply 10 V to cable 3.
Resetting
-
manual resetting
turn the enclosed handle clockwise. -
motorised resetting
apply (0)2 V to cable 3.
BEE-SR-0V - Remotely controlled modulating actuator
The BEE-SR-0V modulating actuator is specifically designed for remote control of smoke control dampers. The position of the damper blade is adjustable by means of a 0 to 10 V connection.
- Access for manual operation
Variants
-
BEE24-SR-0V
Modulating actuator BEE24-SR-0V for the control of the airflow
Unlocking
-
manual unlocking
turn the enclosed handle anti-clockwise. -
remote unlocking
apply (0)2 V to cable 3.
Resetting
-
manual resetting
turn the enclosed handle clockwise. -
motorised resetting
apply 10 V to cable 3.