Operation: manual opening
Press the two blocking hooks carefully to unlock the blades.
Click the fusible link into the holder to lock the blades.
Operation: manual closing
Unlock (close) the damper blades by pushing them towards each other. Carefully unlock the fusible link by pushing it sidewards.
Installation: SC+60L selection of the ventilation valve
Make sure that teh selected valve does not prevent the damper blade from closing (for example if rod is too long in case of a valve with adjustable core).
Installation in rigid wall and floor, sealing mortar
The product was tested and approved in:
- Aerated concrete ≥ 100 mm | EI 60 (ve i o) S - (300Pa) | Mortar | Type of installation: built-in inside a duct, 0-360° | SC+60L Ø 100-200 mm
- Aerated concrete ≥ 150 mm | EI 60 (ho i o) S - (300Pa) | Mortar | Type of installation: built-in inside a duct, 0-360° | SC+60L Ø 100-200 mm
Installation in flexible wall applicable for SCV+60, SC+60L
The product was tested and approved in:
- Metal studs gypsum plasterboard Type A (EN 520) ≥ 100 mm | EI 60 (ve i o) S - (300Pa) | Stone wool ≥ 40 kg/m³ + cover plates | Type of installation: built-in inside a duct, 0-360° | SC+60L Ø 100-200 mm
Installation in flexible wall with gypsum sealing applicable for SC(V)+60
The product was tested and approved in:
- Metal studs gypsum plasterboard Type A (EN 520) ≥ 100 mm | EI 60 (ve i o) S - (300Pa) | Gypsum | Type of installation: built-in inside a duct, 0-360° | SC+60L Ø 100-200 mm
General remarks
- Verify if the blade can move freely.
- The fire damper cartridge must remain accessible for inspection and maintenance.
- Please observe safety distances with respect to other construction elements.
Product-specific remarks
- The installation must comply with the installation manual and the classification report.
- The results obtained in standardised supporting structures according to EN 1366-2 also apply to similar supporting structures with a fire resistance, thickness and density equal to or greater than the supporting structure of the test. More information on standardised supporting structures: https://www.rft.eu/en-gb/page/legal-context/european-regulations/standardised-constructions
- Mounting direction: mounting possible with the axis in any position (0-360°)
- Direction of the airflow: discretionary
- If the product is manipulated in any other way than described in this manual, Rf-Technologies will decline any responsibility and the guarantee will expire!