ZENiX 1FD - Field device for monitoring and controlling 1 motorized fire damper
The ZENiX 1FD field device is used to monitor and control 1 motorized fire damper with 230 V actuator. No configuration is required as it has a predefined device address.
benefits
- Suited for a 230 V fire damper actuator, such as a BFL(T)230, BFN(T)230…
- Predefined address: no need for addressing or configuration of the field device
- Functional also without 230 V power on the field device: it will indicate the current damper position, but will not be able to re-arm the damper without power
- LEDs indicate position of the damper, bus communication and error status
Features
- Connection to one 230 V spring return fire damper actuator
- Nominal voltage: 230 V AC
- Power consumption: 25 mW + actuator consumption
- For wire sizing: 18 VA
- IP54 casing
- CE according to 2004/108/EC and 2006/95/C