MARKAGE MB - Mechanisms

BEN - Remotely controlled servomotor

The BEN servomotor is specifically designed for remote control of smoke control dampers.
  1. Access for manual operation
  2. Plug (ST)

Variants

  • BEN24
    Servomotor BEN 24V
  • BEN230
    Servomotor BEN 230V
  • BEN24-ST
    Servomotor BEN 24V with plug (ST)

Unlocking

  • manual unlocking
    turn the enclosed handle anticlockwise (VRE; VU120) or clockwise (MARKAGE MB; VUW120).
  • remote unlocking
    power cables 1 and 2.

Resetting

  • manual resetting
    turn the enclosed handle clockwise (VRE; VU120) or anticlockwise (MARKAGE MB; VUW120).
  • motorised resetting
    power cables 1 and 3.

Documents Scroll down/right to view the entire table

File Type Format Date
Technical product brochure KIT BEN/BEETechnical datasheet KITpdf [8,388.91 kB]07/04/2021

BEE - Remotely controlled servomotor

The BEE servomotor is specifically designed for remote control of smoke control dampers.
  1. Access for manual operation
  2. Plug (ST)

Variants

  • BEE24
    Servomotor BEE 24V
  • BEE230
    Servomotor BEE 230V
  • BEE24-ST
    Servomotor BEE 24V with plug (ST)

Unlocking

  • manual unlocking
    turn the enclosed handle anticlockwise (VRE) or clockwise (MARKAGE MB).
  • remote unlocking
    power cables 1 and 2.

Resetting

  • manual resetting
    turn the enclosed handle clockwise (VRE) or anticlockwise (MARKAGE MB).
  • motorised resetting
    power cables 1 and 3.

Documents Scroll down/right to view the entire table

File Type Format Date
Technical product brochure KIT BEN/BEETechnical datasheet KITpdf [8,388.91 kB]07/04/2021

BE (MAS) - Remotely controlled servomotor

The BE actuator is specifically designed for remote control of MARKAGE MB smoke control dampers with large dimensions (Hn ≥ 1200 mm).
  1. Access for manual resetting
  2. Plug (ST)

Variants

  • BE24
    Servomotor BE 24V
  • BE230
    Servomotor BE 230V
  • BE24-ST
    Servomotor BE 24V with plug (ST)

Unlocking

  • manual unlocking
    turn the enclosed handle anti-clockwise.
  • automatic unlocking
    n/a
  • remote unlocking
    power cables 1 and 2.

Resetting

  • manual resetting
    turn the enclosed handle clockwise.
  • motorised resetting
    power cables 1 and 3.

BE + BEE - Remotely controlled servomotor

The BE actuator is specifically designed for remote control of MARKAGE MB smoke control dampers with large dimensions (Hn ≥ 1200 mm).
  1. Access for manual resetting
  2. Plug (ST)

Variants

  • BE24 + BEE24
    Servomotor BE 24V + Servomotor BEE 24V
  • BE230 + BEE230
    Servomotor BE 230V + Servomotor BEE 230V

Unlocking

  • manual unlocking
    turn the enclosed handle anti-clockwise.
  • automatic unlocking
    n/a
  • remote unlocking
    power cables 1 and 2.

Resetting

  • manual resetting
    turn the enclosed handle clockwise.
  • motorised resetting
    power cables 1 and 3.

BEE + BEE - Remotely controlled servomotor

The BE actuator is specifically designed for remote control of MARKAGE MB smoke control dampers with large dimensions (Hn ≥ 1200 mm).
  1. Access for manual resetting
  2. Plug (ST)

Variants

  • BEE24 + BEE24
    Servomotor BEE 24V + Servomotor BEE 24V
  • BEE230 + BEE230
    Servomotor BEE 230V + Servomotor BEE 230V

Unlocking

  • manual unlocking
    turn the enclosed handle anti-clockwise.
  • automatic unlocking
    n/a
  • remote unlocking
    power cables 1 and 2.

Resetting

  • manual resetting
    turn the enclosed handle clockwise.
  • motorised resetting
    power cables 1 and 3.

BE + BEN - Remotely controlled servomotor

The BE actuator is specifically designed for remote control of MARKAGE MB smoke control dampers with large dimensions (Hn ≥ 1200 mm).
  1. Access for manual resetting
  2. Plug (ST)

Variants

  • BE24 + BEN24
    Servomotor BE 24V + Servomotor BEN 24V
  • BE230 + BEN230
    Servomotor BE 230V + Servomotor BEN 230V

Unlocking

  • manual unlocking
    turn the enclosed handle anti-clockwise.
  • automatic unlocking
    n/a
  • remote unlocking
    power cables 1 and 2.

Resetting

  • manual resetting
    turn the enclosed handle clockwise.
  • motorised resetting
    power cables 1 and 3.