- Home
- Products
- Smoke control dampers
- KAMOUFLAGE MP 1V120
- Mechanisms
KAMOUFLAGE MP 1V120 - Mechanisms
VA MP MEC - Mechanism for remote controlled unlocking and resetting.
Mechanism for the smoke control shutters AVANTAGE MP and KAMOUFLAGE MP. Remote controlled unlocking and resetting.
Variants
-
VA MP MEC
Mechanism for AVANTAGE MP and KAMOUFLAGE MP.
Options - magnet
-
VD24
Natural magnet 24 V DC -
FDCU
Limit switch 'open/closed' (Incl. exc. for H model)
Unlocking
-
manual unlocking
with the key (delivered in the bag together with the installation guidelines) -
automatic unlocking
n/a -
remote unlocking
remote by connection of 24 V DC or 48 V DC
Resetting
-
manual resetting
turn the key 20° anti-clockwise. Push the actuating arm in the direction of the arrow and pull the shutter into its closed position. Turn the key 15° clockwise. The key blocks in the lock and the door can be pulled into its lock. -
motorised resetting
remote controlled by reversing (2-wire) control or alternating (3-wire) control of the voltage to the motor. After the unlocking or rearmament is complete, the voltage on the motor may be stopped.