KAMOUFLAGE AP 1V120 - Installation

Operation: manual opening

1
Unscrew the finishing cap from the opening in the door. Use the key to do this.
2
Turn the key 20° anti-clockwise and push the shutter into its open position.

Operation: manual closing

1
Turn the key 20° anti-clockwise. Push the actuating arm in the direction of the arrow and pull the shutter into its closed position.
2
Turn the key 15° clockwise. The key blocks in the lock and the door can be pulled into its lock.

Electrical wiring

1
The electrical connection is possible via the 2 corners at the side of the hinges.
2
Drill a hole in the refractory material at the chosen corner(s). The galvanised part at the inside of the shutter is already indented.
3
Pierce an opening in the connection box. Affix the grommet delivered with the product.
4
Lead the cables through the opening. Use the protective sleeve (1), the fixation clips (2) and the plastic cable clamp (3) to attach the cables to the frame. Lead the cables to the connection box through the grommet (4) and connect according to the electrical connection diagram.
Caution: after passing and fixing the cables, you need to seal the drilled hole in the refractory plates around the electrical cables with fire resistant adhesive sealant (BCM f.e.).

Installation in a duct

1
The shutter is fixed in the opening. It can be placed either in the duct, in the duct axis, outside the duct or duct extension or in surface-mounted.
2
Example of installation in a shaft
3
Example of installation in a shaft

Installation into vertical concrete shaft without mounting frame

1
Rotate the four fastening plates on the damper 90° (to the upright position).
The fastening plates are not used for an installation without a mounting frame.
2
Make an opening with dimensions (W+10) x (H+10) mm.
Fix the shutter in the opening using 4 screws and dowels Ø6 x 40 mm.
Connect the mechanism according to the wiring diagram.
Check the mobility of the shutter.

Installation into vertical duct (without a mounting frame): general instructions for all types of ducts (other than concrete)

1
Rotate the four fastening plates on the damper 90° (to the upright position).
The fastening plates are not used for an installation without a mounting frame.
2
Make an opening with dimensions (W+A) x (H+A) mm. A = 2 x thickness sleeve (e) + 10 mm.
Fit a sleeve of the same type of material and thickness as the duct (thickness e) of minimum 105 mm deep in the opening.
Place the shutter in the opening.
Ensure the cables are not trapped at this stage.
Fix the shutter in the opening using 4 screws Ø6 x 40 mm.
Caution: make sure that the screws don't exceed the sleeve's thickness!
Connect the mechanism according to the wiring diagram.
Check the mobility of the shutter.

General remarks

  • The installation must comply with the installation manual and the classification report.
  • The installation of the smoke control duct must comply with the classification report delivered by the manufacturer.
  • Axis orientation: see the declaration of performance.
  • Avoid the obstruction of adjoining smoke control ducts.
  • Verify if the blade can move freely.
  • Rf-t smoke dampers may be applied to smoke control ducts that have been tested according to EN 1366-8 and EN 1366-9 as appropriate, constructed from similar materials with a fire resistance, thickness and density equal or superior to these of the tested materials.
  • Caution: when fitting, the product should be handled with care and remain protected from any sealing products.
  • Caution: before putting the installation into operation, clean off all the dust and dirt.
  • Caution: bear in mind the blade’s clearance inside the smoke control duct.