CU-LT-1S - Classification

Classification Scroll down/right to view the entire table

File Type Wall Sealing Classification
Download Rigid wall Aerated concrete ≥ 100 mm Not applicable EI 120 (ve i o) S - (500 Pa)
Download Rigid wall Aerated concrete ≥ 100 mm Galvanised duct + GEOFLAM® F 45 mm + mortar EI 120 (ve i o) S - (500 Pa)
Download Flexible wall Metal studs gypsum plasterboard Type A (EN 520) ≥ 100 mm Not applicable EI 60 (ve i o) S - (500 Pa)
Download Flexible wall Metal studs gypsum plasterboard Type F (EN 520) ≥ 100 mm Not applicable EI 90 (ve i o) S - (500 Pa)
Download Flexible wall Gypsum blocks ≥ 70 mm Not applicable EI 120 (ve i o) S - (500 Pa)
Download Rigid floor Aerated concrete ≥ 150 mm Not applicable EI 120 (ho i o) S - (500 Pa)

Installation

# Installation