Can minimal distances be applied to fire dampers installed remote from the wall?
Yes. The CR60, CR120 and CU-LT have been certified for installation remote from the wall in combination with an installation at minimal distances. The minimal distances between the dampers (30 or 50 mm) or between the dampers and the ceiling (30 or 25 mm) apply on dampers installed remote of the compartment wall.